A thermal inspection report template clients can actually read

A thermal report is judged by someone who doesn't own a thermal camera. Your client, their electrician or their insurer needs to see what was found, where it is, how serious it is, and what to do, without learning what an ironbow palette is.

A good thermal inspection report has a summary page listing every finding with its priority, then one page per finding showing the thermal and visual images side by side, the measured temperatures (spot or box max, a reference, and the difference), the object parameters used (emissivity, reflected temperature, distance), the conditions at the time (ambient temperature, and load for electrical work), the location, and a recommended action. HeatDeck generates this layout from your selected images in one click, with your logo and notes.

The cover and summary page

  • Client, site address and date of the survey.
  • Inspector name and qualification, and the camera model used.
  • Scope: what was inspected, and what wasn't.
  • Conditions: outdoor and indoor temperature, wind and sun for building work, load for electrical work.
  • A findings table: finding number, location, component, temperature difference, priority, action.

Many clients read only this page. Make it complete on its own.

One page per finding

  • Thermal and visual image side by side, the same framing, with the measurement drawn on the thermal one.
  • Measurements: the hot spot (box max), a reference point on a similar component or the ambient, and the difference (ΔT).
  • Object parameters: emissivity, reflected temperature, distance. This is what makes the number defensible.
  • Location and component, specific enough to find again: panel, row, breaker number.
  • Priority and recommended action, in plain words.

Use the same palette and temperature span on every page where images are compared, so colour means the same thing throughout.

Setting priorities for electrical findings

Many electrical thermographers rank findings by temperature difference using bands similar to the NETA guidance: compared with a similar component under similar load, a ΔT of about 1–3 °C suggests a possible deficiency worth watching, about 4–15 °C a probable deficiency to repair when convenient, and above about 15 °C a major one to repair promptly. Follow the standard or client specification you work to, state which one in the report, and remember that load matters: a connection that is warm at 30% load will be much hotter at full load.

Building envelope reports

For insulation gaps, air leakage and moisture, the essentials are a sufficient indoor-outdoor temperature difference (often at least 10 °C), no recent direct sun on the surface, and the indoor and outdoor temperatures recorded on the summary page. Describe findings as thermal anomalies consistent with a cause ("consistent with missing insulation") unless you confirmed the cause another way, for example with a moisture meter.

Producing it in HeatDeck

Select the images for the report, lock a palette and span, draw your measurements, and add a note per image. The PDF export lays out the cover, the findings table and a page per image with thermal and visual side by side, the measurements, the object parameters and your logo. Images from FLIR and InfiRay / Topdon cameras can sit in the same report.

Generate the report from your images

Thermal and visual side by side, measurements, parameters and your logo, in one click.

FAQ

What should a thermal report include for insurance?

Usually the date, conditions and load at the time, the camera and inspector, each finding with images and temperatures, the object parameters used, and a priority. Check the insurer's own specification first.

Can I put images from different cameras in one report?